Cost-effective
heat removal through a constant flow of clean, ultra-low temperature
coolant
Applications
Heat
exchangers
Jacketed
vessels
Plastic
molding and extrusion
Vacuum
chambers
Plasma
etch equipment
Reaction
cooling
Cloud
and pour point
Features
Benefits
Mechanically refrigerated
Eliminates the cost and potential
hazards associated with dry ice and liquid nitrogen
Small footprint
Saves space
RS-232 interface
Remote operation and monitoring of
all system functions
Caster-mounted
Portability
*Specifications
noted below are dependent on fluid choice, fluid temperatures, ambient
temperature and electrical supply. Please contact the factory to
further discuss your requirements.
Model
Specifications
RC2103
RC2113
RC3111,
3
RC311
GWT1
Heat
Removal (watts/BTUs)
-20°C
1350/4610
1350/4610
3400/11590
3400/11590
-30°C
1250/4260
1250/4260
3000/10230
3000/10230
-40°C
1150/3925
1150/3925
2700/9207
2700/9207
-50°C
1000/3410
1000/3410
2400/8184
2400/8184
-60°C
880/3005
880/3005
1800/6130
1800/6130
-70°C
550/1877
550/1877
1200/4090
1200/4090
-80°C
-
-
500/1705
Temperature
Range °C
-80
to -10
-80
to +75
-90
to +75
-75
to +150
Reservoir
liters
5
5
5
11.6
Compressor
Two
@ 1 hp
Two
@ 1 hp
Two
@ 4 hp
Two
@ 4 hp
Controls
standard:
Digital/RS-232
Deluxe
Digital
Deluxe
Digital
Deluxe
Digital
Control
Stability
±
°C
0.122
0.12
0.3
0.3
Heater
-
1500W
1500W
2500 W
Pump
6
gpm @ 22 PSI
6
gpm @ 22 PSI
6
gpm @ 22 PSI
6
gpm @ 22 PSI
Dimension W x D x H
inches
21
x 29 x 48
21
x 29 x 48
21
x 29 x 57
21
x 29 x 57
cm
53
x 74 x 122
53
x 74 x 122
53
x 74 x 145
53
x 74 x 145
Weight
lbs/kg
390/177
390/177
500/227
500/227
Electrical
208-230V
50-60 Hz 18A
208-230V
50-60 Hz 25A
208-230V
50-60 Hz/3ph
21A
208V/
60 Hz
28A
1.
Water-cooled only.
2. Process dependent.
3. 220V/50 Hz also available. Decreases heat removal by 17%.