*Specifications
noted below are dependent on fluid choice, fluid temperatures, ambient
temperature and electrical supply. Please contact the factory to
further discuss your requirements.
Model
Specifications
UC500
UC500LT1
UC750
UC750LT1
Heat
Removal (watts/BTUs)
+20°C
15500/52850
12500/42625
24000/81910
17000/57970
+10°C
14100/48080
12100/41295
18000/61435
16000/54560
0°C
11100/37850
12000/40955
14000/47780
15000/51150
-10°C
6800/23208
8200/27960
9000/30690
11000/37510
-15°C
-
7300/24915
-
9000/30690
-20°C
-
6000/20460
-
8000/27280
-30°C
-
3600/12285
-
4500/15345
Temperature
Range °C
-15 to +30
-40 to +30
-15 to +30
-40 to +30
Reservoir
liters
21
21
21
21
Compressor
6 hp
6 hp
7.5 hp
7.5 hp
Controls
standard:
Digital/RS-232
Digital/RS-232
Digital/RS-232
option1:
Deluxe Digital
Deluxe Digital
Deluxe Digital
Deluxe Digital
Control
Stability2
±
°C
0.5
0.5
0.5
0.5
Heater (optional)2
-
130°C/4 kW3
or 10 kW4
-
130°C/4 kW3
or 10 kW4
Pump:
Standard: centrifugal
20 gpm @ 45
PSI
20 gpm @ 45
PSI
20 gpm @ 45
PSI
20 gpm @ 45
PSI
option: positive displacement3
8 gpm @ 86
PSI
8 gpm @ 86
PSI
8 gpm @ 86
PSI
8 gpm @ 86
PSI
Dimension W x D x H
inches
37 x 37 x 41
37 x 37 x 41
37 x 37 x 41
37 x 37 x 41
cm
94 x 94 x 104
94 x 94 x 104
94 x 94 x 104
94 x 94 x 104
Weight
lbs/kg
700/318
700/318
800/318
800/318
Electrical5
208/230V
60 Hz/3 ph
208/230V
60 Hz/3 ph
208/230V
60 Hz/3 ph
208/230V
60 Hz/3 ph
1.
When air-cooled units are manufactured with the heater option,
derate the heat removal by 10%.
2. Deluxe Digital Control is required for +130ºC units. (or
380V) and adds 12A to utility requirement.
3. 4 kW heat option for UC500LT and UC750LT adds 11A to utility
requirement.
4. 10 kW heat option for UC500LT and UC750LT requires 460V
5. 220V/50 Hz also available. Decreases heat removal by 17%.